Residual current circuit breaker (RCCB) Doepke

Add to selection
General information
Ordercode YESSS
09167984
Product code
09167984
EAN code
4014712156630
Product group
Residual current circuit breaker (RCCB)
Brand
Doepke
RCCB 4p, 100A, 0.5A, Type B SK, 290/500V, N left RCCB 4p, 100A, 0.5A, Type B SK, 290/500V, N left
Product description

Residual current circuit-breakers (RCCB) switch the power supply off if dangerous high residual currents occur. DFS 4 are two-terminal or two-terminal pair residual current circuit-breakers for single- or three-phase networks. In the standard design, the compact devices are just four module widths wide. They are available with many different residual current types and variants for rated currents up to 125 A. The large two-tier terminals can also accommodate large conductor cross-sections. The trip position of the multi-function toggle switch simplifies fault-finding. The free label software helps in the labelling process. Type B switches are AC-DC sensitive at frequencies of 0 Hz (smooth residual currents) to 150 kHz. They have increased resistance to surge currents and lightning. For residual current circuit-breakers with characteristic curve SK, the frequency response of the tripping current is designed so that residual currents with high frequencies, such as in the clock frequency range for frequency converters, as opposed to the rated frequency are detected with significantly reduced sensitivity. Undesired trips caused by leakage currents can therefore be widely avoided. However, fire protection depending on the rated residual current of the switch (0.03 A, 0.1 A or 0.3 A) is only provided for residual currents with frequencies up to 1 kHz, 300 Hz or 100 Hz, while the devices with tripping current frequency response B+ or NK offer protection over the entire tripping frequency range up to 20 kHz or 150 kHz, respectively. Devices in design V are made for special voltages. Devices in the standard design are intended for monitoring circuits with a rated frequency of 50 Hz. Properties: High level of immunity against leakage and residual currents due to operational conditions from frequency 1 kHz and higher; AC/DC sensitive for residual currents with frequencies and mixed frequencies of 0 Hz (smooth direct current) up to 150 kHz; high availability even of voltage-independent detection of smooth DC residual current and AC residual current with frequencies not equal to 50/60 Hz thanks to full functional compatibility with mains voltages from at least 50 V AC on any two active conductors; mains-voltage-independent tripping when type A residual currents occur; compact design for all rated currents; high short-circuit resistance; double-sided two-tier terminals for large conductor cross-section and busbar; switch position indicator; viewing window for labels; multifunction switch toggle with three positions: "on", "off" and "tripped"; Neutral conductor position left; Mounting: quick fastening to mounting rail; any installation position; supply preferably from above; Application areas: Main distribution boards in power supplies to large areas with TN-S, TT and TN-C-S systems, with sub-distribution boards in which power electronics equipment may be used or connected, such as frequency converters, switching power supplies, high-frequency converters. UPS installations and photovoltaic systems. Selective residual current circuit-breakers in most cases protect the cables from the main distribution board to the sub-distribution boards; Hints: suitable for use in 50 Hz AC networks; RCCBs for other frequencies available upon request; Not designed for use in direct current networks or on the output side of controlled electrical equipment such as frequency converters.

Product specifications
Number of poles
4
Rated current
100 A
Rated fault current
0.5 A
Leakage current type
B
Rated voltage
500 V
Rated insulation voltage Ui
500 V
Rated impulse withstand voltage Uimp
4 kV
Width in number of modular spacings
4
Selective protection
No
Short-circuit breaking capacity (Icw)
10 kA
Built-in depth
69 mm
Additional equipment possible
Yes
Mounting method
DIN rail
With interlocking device
Yes
Frequency
50 Hz
Surge current capacity
3 kA
Degree of protection (IP)
IP20
Ambient temperature during operating
-25 - 40 °C
Short-time delayed tripping
Yes
Pollution degree
2
Connectable conductor cross section multi-wired
1.5 - 50 mm²
Connectable conductor cross section solid-core
1.5 - 50 mm²
Voltage type
AC
Explosion-proof
No
Power loss
24.7 W
RAL-number (similar)
7035