Residual current circuit breaker (RCCB) Doepke

Add to selection
General information
Ordercode YESSS
09112601
Product code
09112601
EAN code
4014712069237
Product group
Residual current circuit breaker (RCCB)
Brand
Doepke
RCCB 2p, 16A, 0.01A, Type A RCCB 2p, 16A, 0.01A, Type A
Product description

Residual current circuit-breakers (RCCB) switch the power supply off if dangerous high residual currents occur. DFS 2 are two-terminal residual current circuit-breakers for single-phase networks. In the standard design, the compact devices are just two module widths wide. They are available with many different residual current types and variants for rated currents up to 125 A. The large two-tier terminals can also accommodate large conductor cross-sections. The trip position of the multi-function toggle switch simplifies fault-finding. The free label software helps in the labelling process. Type A switches are sensitive to pulsating and alternating currents. This function is independent of the mains voltage. Devices in the standard design are intended for monitoring circuits with a rated voltage of 230 V and a rated frequency of 50 Hz. Properties: tripping not dependent on mains and auxiliary voltage; sensitive to AC residual currents and pulsating DC residual currents (type A) compact design for all rated currents; high short-circuit resistance; double-sided two-tier terminals for large conductor cross-section and busbar; switch position indicator; viewing window for labels; multifunction switch toggle with three positions: "on", "off" and "tripped"; Neutral conductor position left or right; Mounting: quick fastening to mounting rail; any installation position; supply from any direction; Application areas: Power supplies to residential and purpose-built buildings as well as industrial facilities with TN-S, TT and TN-C-S networks. In IT networks. the residual current circuit-breakers of this series can be set to switch off in the event of a second fault; Excluded is the application in TN-C systems and for the protection of installations in which electronic equipment could generate smooth DC currents or residual currents with frequencies other than 50 Hz. Comprehensive protection is not provided in this case. For these applications we recommend our AC/DC sensitive residual current circuit-breakers (Type B or B+).

Product specifications
Number of poles
2
Rated current
16 A
Rated fault current
0.01 A
Leakage current type
A
Rated voltage
230 V
Rated insulation voltage Ui
400 V
Rated impulse withstand voltage Uimp
4 kV
Width in number of modular spacings
2
Selective protection
No
Short-circuit breaking capacity (Icw)
10 kA
Built-in depth
69 mm
Additional equipment possible
Yes
Mounting method
DIN rail
With interlocking device
Yes
Frequency
50 Hz
Surge current capacity
0.25 kA
Degree of protection (IP)
IP20
Ambient temperature during operating
-25 - 40 °C
Short-time delayed tripping
No
Pollution degree
2
Connectable conductor cross section multi-wired
1.5 - 50 mm²
Connectable conductor cross section solid-core
1.5 - 50 mm²
Voltage type
AC
Explosion-proof
No
Power loss
1.2 W
RAL-number (similar)
7035
more specifications
^