Earth leakage circuit breaker Doepke

Add to selection
General information
Ordercode YESSS
09164781
Product code
09164781
EAN code
4014712145481
Product group
Earth leakage circuit breaker
Brand
Doepke
Circuit-breaker with RCCB 4-pole, 100A, 0.03A, Type A Circuit-breaker with RCCB 4-pole, 100A, 0.03A, Type A
Product description

Circuit-breakers with residual current trip (CBR) switch high currents, protect equipment, cables and lines against overcurrent and protect people against electric shock. DFL 8 are compact devices with integrated auxiliary switch and terminals for large conductor cross-sections. Type A switches are sensitive to pulsating and alternating currents. This function is independent of the mains voltage. Switches of this variant have a fixed residual response current of 30 mA for the protection of persons. They therefore provide fault and fire protection as well as additional protection (personal protection, protection in the event of direct contact). Standard variant devices are designed for the monitoring of circuits with a rated voltage of 400 V/690 V and a rated frequency of 50 Hz. Properties: fixed rated residual current of 0.03 A; type range with rated currents from 100 A to 250 A; four-pole; rated voltage 400/690 V AC; detection of AC residual currents and pulsating DC residual currents; function range of the residual current trip 0-690 V ; function range of the residual current operated protective device 280-690 V ; trip independent of the mains voltage and auxiliary voltage when overcurrent and residual currents occur; high short-circuit switching capacity; terminals up to 185 mm2; high surge current strength, i.e. low tendency to faulty trips due to transient residual currents; thresholds adjustable for instantaneous and slow-blow overcurrent trip; integrated auxiliary switches; Mounting: mounting on mounting plate; any installation position; supply from any direction; Application areas: power supplies to purpose-built buildings as well as industrial facilities with TN-S, TT and TN-C-S networks with high short-circuit power; In IT networks. the residual current trip of the CBR can be set to switch off in the event of a second earth fault; use for residual current protection in TN-C networks is excluded; Hints: The type A CBR does not provide comprehensive protection in systems containing electronic equipment can cause smooth DC residual currents or residual currents with frequencies not equal to 50 Hz. For these applications we recommend our AC/DC sensitive CBR type B.

Product specifications
Release characteristic
Other
Rated current
100 A
Rated fault current
0.03 A
Rated insulation voltage Ui
1000 V
Rated impulse withstand voltage Uimp
8 kV
Width in number of modular spacings
0
Rated voltage
690 V
Number of poles (total)
4
Number of protected poles
3
Leakage current type
A
Frequency
50 Hz
Disconnection characteristic
Short-time delayed
Rated short-circuit breaking capacity according to IEC 60947-2
85 kA
Concurrently switching neutral conductor
Yes
Over voltage category
3
Surge current capacity
5 kA
With interlocking device
Yes
Pollution degree
3
Voltage type
AC
Built-in depth
149 mm
Anti-nuisance tripping version
No
Degree of protection (IP)
IP20
Ambient temperature during operating
-25 - 70 °C
Connectable conductor cross section solid-core
4 - 16 mm²
Connectable conductor cross section multi-wired
25 - 185 mm²
Power loss
60.8 W
more specifications
^