Residual current circuit breaker (RCCB) Eaton

Add to selection
General information
Ordercode YESSS
3910-5784
Product code
170441
EAN code
04015081669271
Product group
Residual current circuit breaker (RCCB)
Brand
Eaton
Residual current circuit breaker (RCCB), 100A, 2p, 100mA, type S/A Residual current circuit breaker (RCCB), 100A, 2p, 100mA, type S/A
Product description

Residual current circuit-breaker FRCmM, 2 pole, Rated current In: 100 A, Rated short-circuit strength Icn: 10 with back-up fuse kA, Rated fault current IΔN: 0.1 A, Switchgear for industrial and advanced commercial applications

Product specifications
Number of poles
2
Rated current
100 A
Rated fault current
0.1 A
Leakage current type
A
Rated voltage
240 V
Rated insulation voltage Ui
440 V
Rated impulse withstand voltage Uimp
4 kV
Width in number of modular spacings
2
Selective protection
Yes
Short-circuit breaking capacity (Icw)
10 kA
Built-in depth
70.5 mm
Additional equipment possible
Yes
Mounting method
DIN rail
With interlocking device
Yes
Frequency
50/60 Hz
Surge current capacity
5 kA
Degree of protection (IP)
IP20
Ambient temperature during operating
-25 - 40 °C
Short-time delayed tripping
No
Pollution degree
2
Connectable conductor cross section multi-wired
1.5 - 16 mm²
Connectable conductor cross section solid-core
1.5 - 35 mm²
Voltage type
AC
Explosion-proof
No
RAL-number (similar)
7035
more specifications
^